- 20 -
70 0046 Setup
(applicable to
Scale Meter)
M = Meter
F = Function
D = Display
T = Tare
Bits 3:0 Ctrl In 1 Ctrl In 2 Both Reset
Hex 0 M Reset M Hold M Reset
Hex 1 F Reset Peak D M Reset
Hex 2 M Hold Peak D F Reset
Hex 3 M Hold Tare Tare
Hex 4 Peak Tare F Reset
Hex 5 M Reset Tare M Reset
Hex 6 F Reset Tare M Reset
Hex 7 T Reset Tare M Reset
Hex 8 D Blank Tare M Reset
Hex 9 M Reset D Blank M Reset
Hex A F Reset D Blank M Reset
Hex B D Item Tare Tare
Hex C D Item D Blank F Reset
Hex D M Reset D Item M Reset
Hex E F Reset D Item M Reset
Hex F M Hold D Item M Reset
Bit 4 0 = Scale, Offset 1 = Coord of 2 Points
Bit 5 0 = Peak key is Peak 1 = Peak key is Tare
Bit 6 0 = 60 Hz 1 = 50 Hz
Bit 7 0 = No dummy zero 1 = Dummy zero
71 0047 Filter Bits 3:0 Filtering
Hex 0 = Auto Filter, 1 = Batch 16, 2-9 = Moving
Avg, 2 = .08S, 3 = .15S, 4 = .3S, 5 = .6S, 6 = 1.2S,
7 = 2.4S, 8 = 4.8S, 9 = 9.6S, A = Unfiltered
Bit 4 0 = Low Adaptive 1 = High Adaptive
Bit 5 0 = Display Batch of 16 1 = Display Filtered
Bit 6 0 = Peak of Unfiltered 1 = Peak of Filtered
Bit 7 0 = Alarm source Unfiltered, 1 = Filtered
72 0048 Options Do Not Use.
73 0049 Serial Config 1 Bits 3:0 Time between Continuous Serial Outputs
Hex 0=.017S, 1=.28S, 2=.57S, 3=1.1S, 4=2.3S,
5=4.5S, 6=9.1S, 7=18.1S, 8=36.3S, 9=1M13S,
A=2M25S, B=4M50S, C=9M40S, D=19M20S,
E=38M41S, F=77M21S
Bits 6:4 Baud Rate
000 = 300, 001 = 600, 010 = 1200, 011 = 2400,
100 = 4800, 101 = 9600, 110 = 19200
Bit 7 0 = Send Unfiltered value, 1 = Send Filtered Val