SETTING UP COMMUNICATIONS (REMOTE C MODE)
The above screen will appear under the
Communication
tab if
Remote C
has
been selected as
Display Type
under the
Input+Display
tab. This mode is able to
extract data from an ASCII string that
contains multiple data values and non-
numeric characters. Please see the F1
Help screen to the right.
Under this tab, you can reselect
Baud
Rate
,
Device Address
,
Serial Protocol
,
and
Full/Half Duplex
, even though you
may have selected different values to es-
tablish initial communications with your PC.
Set
Output Mode
to
Command
. Ignore
CR(LF)
,
Output Items
,
Output Filter
and
Output Rate
, as
these items apply to digital transmission by a counter-transmitter, not to digital-to-analog
conversion by the serial input transmitter.